Permit Number: T07CM02679
Parcel: 128010190

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02679
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/08/2007 ROBERT SHERRY WATER REVIEW Denied 1. Comment not addressed. If the building is served by a single water meter and currently has a reduced pressure backflow prevention assembly located immediately downstream of the meter, note its presence and size on the drawing. Reduced pressure backflow prevention assemblies shall be installed directly after the water meter for multi-use commercial buildings and for buildings with food service. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
10/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. No valves shall be located between the thermal expansion tank and the water heater. Reference Section 608.3, UPC 2003.
2. Relocate the new reduced pressure backflow preventer to conform to the access and clearance requirements of Section 603.2.3, UPC 2003.
10/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/11/2007 GERRY KOZIOL WWM REVIEW Approved