Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02679
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/25/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/10/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Specify grounding of the telephone system. Identify the size of the grounding conductor and the grounding means. Reference NEC 800.40. 2. Please calculate loading of the Show Room Receptacle branch circuit according to NEC 220.12 (A). 3. Please clarify which lighting is to go on Circuit 28 and which is to go on Circuit 30. If we guess wrong, Circuit 30 may or may not be overloaded. 4. Please submit cut sheets for the lighting fixtures. Show the input volt-amperes for the 250W MH fixtures. Note to Plans Examiner: When volt-amperes per fixture has been documented, verify no overloaded circuits at continuous loading. 5. Please compare the values in the Lighting Application Worksheet to those in Table 9.3.1.2, attached. 6. Please resize the GND between the transformer and Panel C from 2/0 to 3/0. Reference NEC Table 250.66, Footnote a. |
07/10/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Reduced pressure backflow prevention assemblies shall be installed directly after the water meter for multi-use commercial buildings and for buildings with food service. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
07/10/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide waste and vent isometrics. Reference Section 103.2.3, UPC 2003. 2. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003. 3. The manufacturer of the specified thermal expansion tank does not recommend the unit for installation on the hot water side of the water heater. No valves shall be located between the thermal expansion tank and the water heater. Reference Section 608.3, UPC 2003. 4. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference Sections 304.0 and 801.2, UPC 2003. |
07/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the ventilation calculation shown with the air conditioning unit schedule on sheet M1: the outside air quantities are based on six A/C units but only four A/C units are shown. Reference Sections 106.3.1 and 403.2, IMC 2003. 2. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 3. Revise the size of the condensate drains per Section 307.2.2, IMC 2003 as amended by the City of Tucson. |
07/23/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: Beverages & More 2:need to show location/method of connection to on-site private & public sewer |
07/24/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide code analysis on plans for the entire building; whether it's seperated or non-seperated use; note any fire resistance ratings for demising walls. 2. Indicate on plans location of any fire walls that would reduce overall area of building. 3. Provide detail for how wall is to be infilled at side exit pp A1.1 4. Please note on pp A2.1 that emergency lighting and exit sign locations are pp E3. 5. Add vertical grab bar to details 5 & 6 pp A6.1 per 2003 ANSI 117.1 fig 604.5.1. Questions? LeeRay 520-837-4908 LeeRay.Hanly@tucsonaz.gov |
08/16/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |