Permit Number: T07CM02655
Parcel: 10408078C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02655
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2007 TERRY STEVENS ZONING REVIEW Approved
06/22/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Recalculate the ventilation requirements for AC-13 and AC-16 per Section 403.3.2, IMC 2003.
2. Recirculation of the air from the restroom is prohibited. (body shop)
3. Clarify the specifications for EF-1. Restrooms require 75cfm of exhaust per water closet or urinal.
06/22/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/22/2007 ROBERT SHERRY WATER REVIEW Approved
06/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the BTUH input for the relocated water heater.
2. Provide a detail of the water heater installation.
3. Provide descriptions for the new plumbing fixtures.
4. Provide riser diagrams for lounge/restroom plumbing.
06/22/2007 ANY ENGINEERING REVIEW Approved
06/26/2007 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
06/26/2007 CAGUILA1 WWM REVIEW Needs Review
06/26/2007 CAGUILA1 FIRE REVIEW Needs Review
06/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review