Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02655
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/22/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Recalculate the ventilation requirements for AC-13 and AC-16 per Section 403.3.2, IMC 2003. 2. Recirculation of the air from the restroom is prohibited. (body shop) 3. Clarify the specifications for EF-1. Restrooms require 75cfm of exhaust per water closet or urinal. |
| 06/22/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/22/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/22/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the BTUH input for the relocated water heater. 2. Provide a detail of the water heater installation. 3. Provide descriptions for the new plumbing fixtures. 4. Provide riser diagrams for lounge/restroom plumbing. |
| 06/22/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 06/26/2007 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/26/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 06/26/2007 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 06/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |