Permit Number: T07CM02654
Parcel: 108253970

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM02654
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2007 DAVE MANN FIRE REVIEW Approved
07/11/2007 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies shall be installed directly after the main water meter for buildings that have multi-metered water services. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Provide a site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Show also the location and size of the primary water meter. Reference Section 103.2.3, UPC 2003.
07/13/2007 GERRY KOZIOL WWM REVIEW Approved
07/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/18/2007 TERRY STEVENS ZONING REVIEW Approved
07/25/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2007 THAUSER1 OUT TO CUSTOMER Completed
07/26/2007 THAUSER1 REJECT SHELF Completed