Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02638
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2007 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T07CM02638 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Interior alterations require the installation of smoke alarms if not existing, R313.2.1. STRUCTURAL PLANS: 1. Provide brace wall details and notes for exterior frame walls (North wall) showing panels at the ends (within 12.5') of all wall lines, R602.10.6. Or, provide design calculations supporting the non-prescriptive approach. 2. Provide joist sizes (2"x 6" on Section 1/A2.0) in compliance with Table R802.4. SECTIONS - DETAILS - NOTES: 1. Provide consistent material references for the roof surface on Section 1/A2.0 & Detail 3/A3.0, R106.1.1. 2. Show the correct scale on Section 1/A2.0 PLUMBING PLANS: 1. The water fixture unit values on the Connection Schedule should be consistent with 2006 UPC Table 6-5. 2. Clarify the total developed length of 110' as the gas meter is shown near the building. Adding or relocating a gas appliance on the system may require upgrading the pipe size for the connected demand, UPC 1217.0, 1217.2, & Table 12-7. A developed length of 110' requires a 1-ΒΌ" service pipe for over 173 CFH connected load. MECHANICAL PLANS: 1. Show the kitchen exhaust fan minimum 100 CFM rating, M1507.3. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/05/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 11/05/2007 | THAUSER1 | REJECT SHELF | Completed |