Permit Number: T07CM02638
Parcel: 129021790

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM02638
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM02638

· SITE PLAN:
· FOUNDATION
· FLOOR
· STRUCTURAL
· ELEVATION
· DETAIL
· PLUMBING
· MECHANICAL
· ELECTRICAL
· OLC
· IECC

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SITE PLAN:

1. Show the water pipe size from the meter to the building. A new 1" line may be needed to the new water heater. The pipe must be sized for the calculated load, 2006 UPC 610.1.

FOUNDATION PLANS:

1. All slabs (i.e. pads outside of doors) shall be shown and their thickness specified. Indicate the slopes for exterior slabs, R311.4.3.
2. Specify and locate all foundation hold-downs (at quarter points) for brace wall panels, R602.10.3, R602.10.6.

FLOOR PLANS:

2. Show the location of tempered glass adjacent to doorways within 24", R308.4.6.
3. Locate and identify brace wall type, R602.10.3 (include interior wall lines, R602.10.1.1) along with the appropriate tie-downs and nailing schedule, R602.10.8.

STRUCTURAL PLANS:

1. Provide brace wall details and notes for exterior frame walls showing panels at the ends (within 12.5') of all wall lines, R602.10.6.
2. Specify design criteria providing values for roof system dead load, R301.1. The load limit for the existing 2"x 6" rafters may be exceeded.
3. Provide joist sizes (Section 1/A2.0) in compliance with Table R802.4.

SECTIONS - DETAILS - NOTES:

1. If the Pima County Inclusive Home Design Notes are included on T1.0 then update the code reference (Note #2) from 2003 IRC to 2006 IRC, R106.1.1.
2. Correct the Footing detail reference shown as 3/A3.0 at the Building Section on A2.0
3. Show an appropriate roof slope for Concrete Tile Roofing (min 2 ½":12), R905.3.
4. Specify veneer anchoring method, weepholes and support (ties or approved reinforcement), R703.7.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code (all call-outs on P1.0), or appeal to the Building Official for IRC design approval.
2. Provide a fixture unit schedule (revise schedule) per 2006 UPC Tables 6-4 and 7-3.
3. Provide the correct total developed length (200 ft ?) from meter to the most remote appliance on the system, and size the supply pipe for the connected demand, UPC 1217.0, 1217.2, & Table 12-7. A developed length over 30' requires a 1 ¼" service pipe for the 344 CFH connected load.

MECHANICAL PLANS:

1. Revise sheet M1.0 showing 2006 IRC at Note #1.

ELECTRICAL PLANS:

1. Show the correct scale on the Electrical Plan, E1.0.
2. Show the circuit number at panel schedule for circuit #22, E3603.5.


If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/23/2007 GERRY KOZIOL WWM REVIEW Approved