Permit Number: T07CM02556
Parcel: 140121420

Address:
2318 E NEVADA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02556
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2007 SREEVES1 2ND PARTY REVIEW REVIEW Denied July 5, 2007

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701


RE: KUCZ RESIDENCE – 1ST REVIEW
CITY OF TUCSON LOG NO. T07CM02556
WILLDAN PROJECT NO. 13881-7060

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
R-3 N/A V-B 560 No No

ARCHITECTURAL COMMENTS:
Sheet 5
Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, Dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2.

Cross-sections shall be cross-referenced to the floor plan and framing plans. Reference IRC Section R106.1.1.

STRUCTURAL COMMENTS:
Sheet 2
Indicate the slope for exterior slabs. Reference IRC Section R311.6.1.

All foundation hold-downs and anchor-bolt spacing for brace walls shall be specified and located on the foundation plan. Reference IRC Section R106.1.1.

Locate and identify brace wall types and locations, along with the appropriate nailing schedule. Reference IRC Section R106.1.1.

Sheet 5
Specify manufacturer and series on glue-lams. Reference IRC Section R106.1.1.

Show details for all bearing and critical conditions. Reference IRC Section R106.1.1.

Indicate and note post size, double or triple studs, and coordinate with foundation plan. Reference IRC Section R106.1.1.

Detail all brace wall connections from the foundation to the roof plywood. Reference IRC Section R106.1.1.

PLUMBING COMMENTS:
Sheet 3
Show the size of the required clean-outs. Reference City of Tucson Submittal Requirements and Section 707.4 #1 of the 2003 UPC.

Waterline: Provide the total fixture unit demand (based on Tables 6-4 & 7-3 or Tables L-1 & L-2) and the maximum developed length. Reference UPC Section 610.

The City of Tucson has adopted the 2003 Uniform Plumbing Code with local amendments. All plans must reference the 2003 UPC with local amendments in its entirety.

MECHANICAL COMMENTS:
Sheet 3
Show on the plans the required kitchen exhaust hood and exhaust duct terminations. Reference IRC Section M1502.1.

Show on the plans how mechanical fresh air will be provided if using one of the non-vented roof methods. Reference Non-Vented Roof Details Dated 7/18-19/2001.

Dryer exhaust systems shall be independent of all other systems and shall convey the moisture to the outside of the building. Revise plan. Reference IRC Section M1501.1.

ELECTRICAL COMMENTS:
Sheet 4
Note that at least one 20-amp branch circuit shall be installed to serve the laundry room and this circuit shall have no other outlets. Reference IRC Sections E3603.3, E3801.8.

Please provide cut sheets for all the exterior light fixtures shown or noted on plans. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. Please provide cut sheets and calculations for all exterior lighting fixtures, including existing. Reference City of Tucson Outdoor Lighting Code.

Please specify how many lamps of each type are being used for the exterior lighting, including existing. Lumens will be calculated by the maximum allowed watts for each fixture that the manufacturer specifies. Reference City of Tucson Outdoor Lighting Code.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference City of Tucson Submittal Requirements.
ENERGY CODE COMMENTS:
Sheet 2
Indicate on the plan the “R” values of insulation, as well as the “U” values of the windows, skylights, and doors in compliance with the energy calculations provided or prescriptive requirements of Chapter 11. Reference IRC Section R106.1.1.

Please submit the required energy code calculations by using the “RES” check program, Chapter 11 of the IRC, or the 2003 IECC, and also annotate on the plans. Reference IRC Section R106.1.1.

Sheet 4
Provide a note that water heaters with vertical pipe risers shall have a heat trap on both the inlet and outlet of the water heater, unless the water heater has an integral heat trap or is part of a circulating system. Reference IECC Section 504.7.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.


Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CK/jk
07/25/2007 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2007 SUE REEVES OUT TO CUSTOMER Completed
07/25/2007 SUE REEVES REJECT SHELF Completed