Permit Number - T07CM02550
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T07CM02550
Building Plan (3rd Review)

TRANSMITTAL DATE: September 12, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved and stamped development plan. Please submit two copies of the approved and stamped development plan, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm02550.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
09/12/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's Do Apply; Central District; 191,411 Square Feet Retail; $601,080.54

Waiting on carolyn for demolition permit to offset impact fee's
09/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/22/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
2. Clarify how the "% Usable Area" was determined. For example, the entry vestibules are considered to be corridors for the calculation of the required ventilation rates and are not "0% usable area". Reference Section 403.3, IMC 2006 as amended by the City of Tucson.
3. Provide ventilation for the bakery/deli area. Reference Section 403.3, IMC 2006 as amended by the City of Tucson.
09/29/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2008 LOREN MAKUS ENGINEERING REVIEW Denied cannot approve plan until DP is approved.
10/01/2008 SREEVES1 WWM REVIEW Needs Review Waiting for information from Carolyn to resubmit to WWM for review