Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM02544
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02544
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. For the equipment associated with the Kiosk, provide location of all outlets, fixtures, switches, appliances, panels, motors, disconnects, and electrical
Equipment, on sealed drawings. Minimum font size 1/8".
2. For the equipment associated with the Kiosk, assign circuit to each receptacle, light, appliance, disconnect, electrical equipment, and indicate panel number on all home runs, on sealed drawings.
3. For the equipment associated with the Kiosk, provide panel schedule, on sealed drawings.
4. Demonstrate compliance with the 2003 IECC for any additional lighting fixtures.
07/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Currently, the applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments (see sheet P-1, Specifications).
2. Provide backflow protection for the coffee brewer per Section 603, UPC 2003.
3. Provide an upper terminal cleanout for the south floor sink. Reference Section 707.4, UPC 2003.
4. The indirect waste piping from the ice machine and the dipper well shall not be combined. Reference Section 801.2.3, UPC 2003.
5. Revise the floor sink detail to note that the minimum distance from the trap weir to the inner edge of the vent shall be two diameters of the trap arm. Reference Section 1002.2, UPC 2003.
07/16/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
07/19/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2007 DELMA ROBEY OUT TO CUSTOMER Completed
08/22/2007 DELMA ROBEY REJECT SHELF Completed