Permit Number: T07CM02543
Parcel: 136261260

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02543
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Currently, the applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments (see sheet P-1, Specifications).
2. Provide backflow protection for the coffee brewer per Section 603, UPC 2003.
3. The indirect waste piping from the ice machine and the dipper well shall not be combined. Reference Section 801.2.3, UPC 2003.
4. Revise the floor sink detail to note that the minimum distance from the trap weir to the inner edge of the vent shall be two diameters of the trap arm. Reference Section 1002.2, UPC 2003.
07/10/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. For the equipment associated with the Kiosk, provide location of all outlets, fixtures, switches, appliances, panels, motors, disconnects, and electrical
Equipment, on sealed drawings. Minimum font size 1/8".
2. For the equipment associated with the Kiosk, assign circuit to each receptacle, light, appliance, disconnect, electrical equipment, and indicate panel number on all home runs, on sealed drawings.
3. For the equipment associated with the Kiosk, provide panel schedule, on sealed drawings.
4. Demonstrate compliance with the 2003 IECC for any additional lighting fixtures.
5. Bracing of Starbuck's Panel not sufficient for Available Fault Current. If existing ISC was taken from previous design documents, please state so on the plans. Otherwise, provide TEP fault current and fault calculations.
07/16/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
07/19/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2007 THAUSER1 OUT TO CUSTOMER Completed
10/05/2007 THAUSER1 REJECT SHELF Completed