Review Details: SITE

Permit Number - T07CM02471
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2007 DAVE MANN FIRE REVIEW Denied 1) Please provide dimension to adjacent proposed hanger location.
2) Fire hydrant is too close to building. Please contact Fire Department (Dave Mann or Harvey Brown 791-3234) for direction.
07/30/2007 STEVE SHIELDS ZONING HC SITE REVIEW Denied See Zoning Comments
07/30/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Arizona Aviation Associates, LLC.
T07CM02471
Site Plan (1st Review)

TRANSMITTAL DATE: July 30, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and
Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for area of expansion only.

2. Based on the current City of Tucson Zoning map, this property is zoned I1 and is not part of the Tucson Airport Authority. As there is not a use specified on the plan Zoning has review this site plan as a Transportation Service, Air Carrier. This said per LUC Sec. 2.7.2.2.C, Transportation Service, Air Carrier is not an allowed use within the I1 zone. Provide documentation which that allows this use within the I1 zone or documentation which supports this lot being part of the Tucson Airport Authority. Additional comments maybe forth coming.

3. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

I:\planning\site\t07cm02471.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
07/30/2007 SSHIELD1 ADA REVIEW Passed
08/01/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond DATE: August 1, 2007
REVIEWER: Elizabeth Eberbach, PE
ACTIVITY NUMBER: T07CM02471
SUBJECT: Tucson Airport Authority 1840 E VALENCIA RD submittal Site Plan Review
LOCATION: The eastern portion of parcel in NE4 NE4 NE4 1.49 AC Section 18 T15S-R14E
WARD: 5

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed plan submittal. Engineering Division recommends conditional approval. Resubmittal required prior to Engineering stamping plans.

CONDITIONAL APPROVAL:
1) Submit copy of master plan drainage report showing that any drainage or basin requirements are met within master plan.

For resubmittal, provide a copy of the Master Drainage Report and a response letter. Call if you have any questions, I can be reached at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
08/08/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. According to the City of Tucson Zoning map, this property is zoned I1 and appears not be part of the Tucson Airport Authority. Provide documentation that allows use within the I1 zone or documentation that indicates lot being part of the Tucson Airport Authority.

2. A separate landscape plan may be needed to verify the entire site meets minimum requirements of LUC 3.7.2.

3. An NPPO plan or Application for Exception may also be needed per LUC 3.8.2.4 & DS 2-15.0.

4. Additional comments may apply.
08/09/2007 ANDREW CONNOR NPPO REVIEW Denied An NPPO plan or Application for Exception may also be needed per LUC 3.8.2.4 & DS 2-15.0.
08/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2007 GERARDO BONILLA OUT TO CUSTOMER Completed