Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02469
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2007 | Michael Wyneken | ZONING-CITY HALL | REVIEW | Approved | |
| 08/21/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning approves the site portion of the project. The building portion of the project is denied based on structural plans for the monopole not being submitted. |
| 08/21/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: August 21, 2007 ACTIVITY NUMBER: T07CM02469 PROJECT NAME: Cell Tower PROJECT ADDRESS: 1240 North 7th Avenue PROJECT REVIEWER: Patricia Gilbert FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION 1. The submitted floodplain use permit application should have an activity number (permit number). When resubmitting the plans to the permit counter pay for the floodplain application/permit and an activity number will be issued. 2. Revise the site plan on sheet A-0 and A-1 to provide the following notes: a. The water surface elevation = 2381.60 NAVD 1988 per flood study by JE Fuller Hydrology & Geomorphology Inc. May 18th, 2006. b. The lowest floor and equipment elevation must be at or above 2382.60 NAVD 1988. 3. Clearly indicate on the plan the finish floor (slab) elevation and equipment elevation on sheet A-0 and A-1. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/27/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/27/2007 | GERARDO BONILLA | REJECT SHELF | Completed |