Permit Number: T07CM02466
Parcel: 11103181E

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM02466
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2009 DAVE MANN FIRE REVIEW Approved
04/29/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
04/29/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: April 29, 2009
ACTIVITY NUMBER: T07CM02466R
PROJECT NAME: Hazen Office Building
PROJECT ADDRESS: 3314 North Country Club Road
PROJECT REVIEWER: Bianca Ramirez, CFM, Engineering Associate

The following items must be revised or added to the site plan prior to approval.

RESUBMITTAL REQUIRED: SITE PLAN

1. Please include a comment letter outlining each change on the revised site plan. Specifically indicate why sidewalks and driveway apron have been deleted from site plan.

2. Correct numbering of pages 1 of 3, 2 of 3 and 3 of 3.

3. Please note that site plan and grading plan must match. Specifically, call out depressed curbs on site plan.

4. Additional comments may be following.

If you have any questions, please contact me at bianca.ramirez@tucsonaz.gov or 520-837-4928.

Bianca Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928
(520) 879-8010 fax
05/04/2009 ANDREW CONNOR NPPO REVIEW Approved
05/04/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Submit previously approved landscape plan with next submittal for reference.

2. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

3. Ensure that all Engineering comments and concerns are addressed.

4. Additional comments may apply.
05/14/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Hazen Office Building
T07CM02466
Site Plan (Revision - 1st Review)

TRANSMITTAL DATE: May 14, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. There is an existing telephone pedestal shown north of the entrance off of N. Cardi Blvd that appears to be within the proposed sidewalk, please clarify.

3. Please explain why sheets 2 of 3 and sheet 2.0 both have site plans. It appears that sheet 2.0 should be the revised site plan.

4. Based on the last approved site plan in The City of Tucson's records, approved by the Zoning review section on 08/15/08, see attached plan, this revision should be revision 4, please clarify.

5. Ensure that all changes to the site plan are reflected on the landscape plan.

6. Additional comments may be forth coming depending on how each comment has been addressed.

7. Once the above comments have been addressed Zoning is will to provide an over-the-counter review. Please call or email to schedule an appointment for this over-the-counter review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm02466R.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/18/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved