Permit Number: T07CM02443
Parcel: Unknown

Address:
2331 E ADAMS ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02443
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/16/2007 MARTIN BROWN FIRE REVIEW Approved
07/31/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please demonstrate that additional 288A does not overload existing service. That is not clear on the plans. In so doing, please consider 25% for the largest motor and loading on Panel AC: (2) (25.1) + (2) (3.1) = 56.4A (360) = 20,304VA, or 6.8KVA per phase, not 6.5.
2. Mechanical specifies 80A maximum fuse size for the CC HP units. See notes under Compressor-Condenser Schedule Sheet MO.1. No such fuse specified on Electrical plans, just the breakers at the panel.
3. Keynotes 7 and 8 were used twice each on the One-Line Diagram. Please verify application.
4. There is a notation on the One-Line Diagram pertaining to the feeder between the wireway and a 200A disconnect. It calls for (2) #6 to the panel, but from where? It calls for (2) 3/0 to a tap inside a gutter, but from where?
08/01/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
08/08/2007 GERRY KOZIOL WWM REVIEW Passed
08/10/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the rise and total length of the common vent for the two furnaces and the relocated water heater. Provide calculations to show how the common vent has been sized. Reference Section 504, IFGC 2006.
2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, 608.3, and 608.5 UPC 2006.
3. Specify the methods and materials to be used to provide fire stopping for penetrations of fire-rated assemblies. Reference Section 1502.1, UPC 2006.
08/10/2007 ROBERT SHERRY WATER REVIEW Approved
08/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations (ASHRAE 62.1) to comply with the requirements of Section 403.3, IMC 2006, as amended by the City of Tucson: the occupant density used for calculations must be at least equal to the default occupant density (Table 6-1).
2. The refrigerant quantities for AHU-1 and AHU-2 (20.9 pounds R-22 per circuit) appear to be greater than indicated by Table 1103.1 for use without a machinery room. Revise the design of the east and west equipment rooms per Section 1105, IMC 2006.
08/15/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: August 15, 2007
ACTIVITY NUMBER: T07CM02443
PROJECT NAME: Install Mechanical Equipment
PROJECT ADDRESS: 2331 East Adams Street
PROJECT REVIEWER: Patricia Gilbert


RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION

SUBMITTAL REQUIRED: COST ESTIMATE FROM A LICENCED CONTRACTOR

1. Improvements to an Existing Nonconforming structure in a City of Tucson Regulatory Flood Hazard Area can not exceed 50% of the value of the structure (the full cash value of the structure as shown on the latest assessment rolls of the county assessor). The contractor's estimate (labor and materials) of the improvement to the structure was not submitted. Submit a contractor's estimate for the proposed work with a floodplain use permit application.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
08/31/2007 CINDY AGUILAR REJECT SHELF Completed