Permit Number: T07CM02429
Parcel: 12510004B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02429
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/15/2007 ANY ENGINEERING REVIEW Approved
06/15/2007 STEVE SHIELDS ZONING REVIEW Approved
06/15/2007 DAVE MANN FIRE REVIEW Approved
06/18/2007 GERRY KOZIOL WWM REVIEW Approved
06/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02429 6/19/07

1. Provide a Load Summary including electrical loads on all previously approved plans for this service entrance.
2. Mechanical calls for 230V power for the Water Heater. Electrical supply is at 208V. Please coordinate with Mechanical and clarify.
06/19/2007 ROBERT SHERRY WATER REVIEW Approved
06/19/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
06/19/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide minimum plumbing fixtures per chapter 29, IBC 2003.