Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02429
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/15/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 06/15/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/15/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/18/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide minimum plumbing fixtures per chapter 29, IBC 2003. |
| 06/19/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02429 6/19/07 1. Provide a Load Summary including electrical loads on all previously approved plans for this service entrance. 2. Mechanical calls for 230V power for the Water Heater. Electrical supply is at 208V. Please coordinate with Mechanical and clarify. |