Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02429
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/12/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/15/2007 | ANY | ENGINEERING | REVIEW | Approved | |
06/15/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/15/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
06/18/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02429 6/19/07 1. Provide a Load Summary including electrical loads on all previously approved plans for this service entrance. 2. Mechanical calls for 230V power for the Water Heater. Electrical supply is at 208V. Please coordinate with Mechanical and clarify. |
06/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/19/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide minimum plumbing fixtures per chapter 29, IBC 2003. |