Review Details: COMMERCIAL TI

Permit Number - T07CM02426
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2007 ANY ZONING REVIEW Active
06/12/2007 ANY ENGINEERING REVIEW Active
06/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02426 6/12/07

1. RTU-1 is existing according to the Mechanical Equipment Data, Electrical Panel Schedule and Mechanical Plan, but new on the Single Line Diagram. Please clarify.
2. Provide electrical requirements for RTU-2, and any other new equipment.
3. Provide feeder size for RTU-2.
4. RTU-2 goes on Panel P according to the panel schedule. Show Panel P on the Line Diagram.
5. 24094/120 = 201 A. Phase A of Panel P appears to be overloaded.
06/12/2007 ANY FIRE REVIEW Active
06/12/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE VERIFICATION THAT THE EXISTING STRUCTURAL COMPONENTS CAN SUPPORT THE NEW MECHANICAL EQUIPMENT PER SECTION 106.1.1 OF THE 2003 IBC. PLEASE ALSO SPECIFY THE WEIGHT OF THE UNIT ON THE PLANS.
06/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size to 1/8" minimum, all uppercase.
2. Show how RTU-2 is to be controlled.
3. Show that the roof structure is capable of supporting the new rooftop unit. Provide the installed weight of the new rooftop unit.
4. Clarify how the space is ventilated.
5. Show the size, route, and termination of the condensate drain for RTU-2.