Permit Number: T07CM02414
Parcel: 10712231B

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM02414
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2007 DAVID RIVERA ZONING REVIEW Approved
11/15/2007 DAVID RIVERA ZONING HC SITE REVIEW Approved
11/19/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approv-Cond DATE: November 19, 2007
SUBJECT: Site Plan - Multifamily
TO: COPE Multi-family housing
LOCATION: 2820 North Castro Avenue, T13S R13E Sec36, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM02414

RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan for the above referenced property. Engineering Division has conditionally approved the site plan. The following items need to be addressed for next submittal for property:

1. Grading permit is required where a separate grading review is required. When submitting the grading plan, include a copy of the last approved site plan.


If you have any questions, I can be reached at 520-837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
11/20/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A 5' wall is required to screen office zoned properties from vehicle use area per LUC Table 3.7.2-I.

2. Revise the landscape plan to show the locations, height and materials for proposed or required screen walls as shown on the site plan per DS 2-07.A.3.

3. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four(4) feet in width, must be provided for each canopy tree within vehicle use area. Verify planter width for tree adjacent to pedestrian access.

4. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

5. Additional comments may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
12/10/2007 SUE REEVES REJECT SHELF Completed