Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM02364
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02364 8/8/07 1. MBIA would not be the panel to power the sump pumps from, because they it would have been designed to carry the load of the modular. Please find a different power source or demonstrate otherwise. 2. Provide panel schedule and load calculations for the additional pumps. 3. Electrical plans refer to existing Panel R1. This is a new panel according to the panel schedule. 4. Show the location of T1 on the plans. Reference NEC 240.21. 5. Modulars take 120/240V power. Justify providing 120/208V power. 6. Provide power requirements for the new sump pumps. |
| 08/08/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/15/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |