Permit Number: T07CM02364
Parcel: 13104399H

Address:
4777 E 29TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM02364
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02364 8/8/07

1. MBIA would not be the panel to power the sump pumps from, because they it would have been designed to carry the load of the modular. Please find a different power source or demonstrate otherwise.
2. Provide panel schedule and load calculations for the additional pumps.
3. Electrical plans refer to existing Panel R1. This is a new panel according to the panel schedule.
4. Show the location of T1 on the plans. Reference NEC 240.21.
5. Modulars take 120/240V power. Justify providing 120/208V power.
6. Provide power requirements for the new sump pumps.
08/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved