Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02357
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/10/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please indicate occupant loads in each classroom and assembly room on plan. 2) Indicate on plan what room at south-west corner is used for as it is on egress route. 3) Show mezzanine level and egress route from mezzanine. 4) Eastern exit from proposed activity room has keynotes indicating both locks and panic bars. You may not have lock on an exit equipped with a panic bar. 5) Please indicate location of required drinking fountains for verification of compliance with table 2902 of the 2003 IBC. |
| 07/11/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/11/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for educational occupancy. |
| 07/11/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. |
| 07/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Demonstrate compliance with NEC 518.4. |
| 07/23/2007 | SREEVES1 | WWM | REVIEW | Needs Review | cannot be reviewed until plumbing has approved plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2007 | DELMA ROBEY | APPROVAL SHELF | Approved |
| 07/23/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 07/23/2007 | DELMA ROBEY | REJECT SHELF | Completed |