Permit Number: T07CM02349
Parcel: 11451218A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02349
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/07/2008 STEVE SHIELDS ZONING REVIEW Approved
04/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Section 1101.11.2.1, UPC 2006, states that the minimum width of a scupper shall be equal to the circumference of the required roof drain from Table 11-1, UPC 2006. The minimum width of a scupper for an area requiring a 3" roof drain would then be 9.4" and 12.6" for an area requiring a 4" roof drain.
04/22/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Since it has been determined that, with the firewall, there will be two services to both Building W and Building E, provide the placards required by NEC 230.2 (E). Specify the exact wording on the plans. This comment was made on the previous submittal. Exact wording has not been specified. For example: "Provide a placard at service A with the following wording: "Service A. Service B located 45' east." "

Work up similar language for all of the services, A, B, C, and D.


2. Sign and date seal on new Sheet MPS. This comment was made on the previous submittal. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008)
04/30/2008 GERRY KOZIOL WWM REVIEW Approved
05/20/2008 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2008 CPIERCE1 OUT TO CUSTOMER Completed
06/03/2008 SUE REEVES REJECT SHELF Completed