Review Details: OTHER

Permit Number - T07CM02348
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the provided ventilation calculations using the correct area of operation and section 403.3 of the local amendments for the allowable use of ASHRAE 62.1. (Note: you may wish to use the IMC calculation method for a kitchen)
2. Show that the sum of the outside air and the transferred air from adjacent spaces is equal to a minimum of 1.5 CFM/SF. Reference footnote f, Table 403.3, IMC 2003.
3. Provide a design for the Type I grease hood and the Type II kitchen exhaust hood including installation details and support from the building structure. Reference Sections 506 and 507, IMC 2003.
4. Show that the design of the make up air ducts for the Type I hood compies with the requirements of Section 506.3.1.2, IMC 2003.