Permit Number: T07CM02348
Parcel: 115180050

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02348
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
12/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Keynote #9 on sheet P-3 indicates that a new grease interceptor will be installed. Provide the size, location, and installation details for the new grease interceptor. Reference section 103.2.3, UPC 2003.
2. Provide fixture descriptions (or material standards) for all plumbing fixtures. Reference Section 401.1, UPC 2003.
3. Show how backflow protection will be provided for the directly connected appliances (e.g. dishwasher, ice makers, steamer, etc). Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
5. Provide floor drains for the pot sinks, scullery sinks, dishwasher, etc, per Section 704.3, UPC 2006.
6. Provide justification for the 2-compartment sinks being indirectly wasted. Reference Sections 103.2.3, 704.3, and 801.2.3, UPC 2003.
7. Coordinate the waste & vent diagram (1/P-5) with the plumbing plan, P-4 and finish labeling the pipe sizes. Reference Section 103.2.3, UPC 2003.
8. Show how the existing floor sinks are vented and if the existing vents are connected to the new venting system. Reference Sections 103.2.3, 901.0, and 904.1, UPC 2003.
9. Show that the two floor sinks for the bar are adequately sized for the appliances and fixtures that are draining to them. Reference Section 702.0, 703.0, and footnote 1, Table 7-3, UPC 2003.
10. Provide adequate information for the review of the gas piping (e.g. pipe sizes, appliance loads and developed lengths for all new and existing appliances served by the existing gas meter. Reference Sections 103.2.3 and 1209.1, UPC 2003.
12/28/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2008 DELMA ROBEY OUT TO CUSTOMER Completed