Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM02348
Parcel: 115180050

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02348
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.
PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Equipment Grounding Conductor for the Panel E feeder shall be sized per Table 250.122 for each parallel run, or #1, not #2. Reference NEC 250.122 (F) (1).
2. Fault calculations for used the value for 2 sets of 50' of 3/0 for the run from the service to Panel E. This run is comprised of 2 sets of 350 MCM, and New Distribution Panel E is shown immediately adjacent to the service. It appears that the fault current at Panel EB is aprox. 15.7 kA, not 12.3, at Panel EB. If the lower value remains on the plans, it could open the question of providing a panel only rated 14K.
3. Fault calculations for used the value for 2 sets of 50' of 3/0 for the run from the service to Panel M. The run itself is 20' of 500 MCM. It appears that the fault current at Panel M is aprox. 25.5 kA, not 19.3, at Panel M, exceeding its fault current rating. This also effects Panel A.
09/20/2007 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
09/20/2007 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review