Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.
PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Equipment Grounding Conductor for the Panel E feeder shall be sized per Table 250.122 for each parallel run, or #1, not #2. Reference NEC 250.122 (F) (1).
2. Fault calculations for used the value for 2 sets of 50' of 3/0 for the run from the service to Panel E. This run is comprised of 2 sets of 350 MCM, and New Distribution Panel E is shown immediately adjacent to the service. It appears that the fault current at Panel EB is aprox. 15.7 kA, not 12.3, at Panel EB. If the lower value remains on the plans, it could open the question of providing a panel only rated 14K.
3. Fault calculations for used the value for 2 sets of 50' of 3/0 for the run from the service to Panel M. The run itself is 20' of 500 MCM. It appears that the fault current at Panel M is aprox. 25.5 kA, not 19.3, at Panel M, exceeding its fault current rating. This also effects Panel A.
09/20/2007 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
09/20/2007 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review