Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02343
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | OK |
| 10/18/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/23/2007 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T07CM02343 10/18/07 1. Rooftop GFCI shall not be connected to load side of disconnecting means for equipment. Reference NEC 210.63 MADE ON 9/25/07. 2. Load in Ckt 37 with lighting fixtures does not tally wattages. Please do so, and verify compliance with NEC 210.23 (A) (1). 3. Check load for Ckt 39. Note that EC-1 load of 8.4A at 120V would be 1008VA, not 617W. 4. Demonstrate source efficacy of 60 lumens per watt. Reference 2006 IECC 505.6.1. COMMENT MADE ON 9/25/07 and 10/2/07. 5. Refer to the following form the Arizona State Board of Technical Registration Regulations: "32-143. Exceptions An architect, geologist, engineer or landscape architect registered under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project." Based upon the plans and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer. |