Permit Number: T07CM02343
Parcel: 11105026D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02343
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02343 10/02/07

1. Provide an electrical circuit for the rooftop GFCI. COMMENT MADE ON 9/25/07. NOTE THAT PANELS ARE LIMITED TO 42 OVERCURRENT DEVICES. REFERENCE NEC 408.35. STANDARD PANEL OF THIS SORT WOULD BE LIMITED TO 42 SPACES FOR SUCH.
2. Provide a cut sheet for the lighting fixtures. COMMENT MADE ON 9/25/07.
3. Demonstrate source efficacy of 60 lumens per watt. Reference 2006 IECC 505.6.1. COMMENT MADE ON 9/25/07.
10/09/2007 GBONILL1 WATER REVIEW Needs Review
10/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/09/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
10/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved