| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02343 10/02/07 1. Provide an electrical circuit for the rooftop GFCI. COMMENT MADE ON 9/25/07. NOTE THAT PANELS ARE LIMITED TO 42 OVERCURRENT DEVICES. REFERENCE NEC 408.35. STANDARD PANEL OF THIS SORT WOULD BE LIMITED TO 42 SPACES FOR SUCH. 2. Provide a cut sheet for the lighting fixtures. COMMENT MADE ON 9/25/07. 3. Demonstrate source efficacy of 60 lumens per watt. Reference 2006 IECC 505.6.1. COMMENT MADE ON 9/25/07. |
| 10/09/2007 | GBONILL1 | WATER | REVIEW | Needs Review | |
| 10/09/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/09/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |