Review Details: RESUBMITTAL
Permit Number - T07CM02343
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Denied | NOTE PREVIOUS COMMENTS APPLY CLARIFY DETAILS COMMENT CLARIFIED AT THE REQUEST OF THE CLIENT BY RAB ON 9/26/07 THE DETAILS DO NOT REFLECT THE PROPOSED CONSTRUCTION. TEH FRONT WALL DETAILS DO NOT REFLECT THE CONSTRUCTION. PROVIDE DETAIL FOR THE CONNECTION OF THE I JOIST TO THE TOP OF THE WALL. CLEARLY INDICATE THE CONSTRUCTION OF THE MASONRY WALL. CLEARLY ILLUSTRATE THE DETAILS FOR THE BEAM TO COLUMN CONNECTIONS CLEARLY ILLUSTRATE THE CONSTRUCTION OF THE MASONRY COLUMNS SUPPORTING THE BEAM PROVIDE DETAILED SECTIONS THROUGH THE BUILDING ILLUSTRATING THE CONSTRUCTION. MORE THAN ONE SECTION WILL BE REQUIRED. FRONT SPAN OF I JOIST APPEARS TO BE OVER SPAN |
| 09/25/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02343 9/25/07 1. Provide an electrical circuit for the rooftop GFCI. 2. Provide a cut sheet for the lighting fixtures. 3. Demonstrate source efficacy of 60 lumens per watt. Reference 2006 IECC 505.6.1. 4. Provide Disconnecting Means for EC-1. Reference NEC 430 Part IX. 5. Clarify undefined symbol in center of Electrical Plan. |
| 09/25/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |