Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Denied NOTE PREVIOUS COMMENTS APPLY
CLARIFY DETAILS

COMMENT CLARIFIED AT THE REQUEST OF THE CLIENT BY RAB ON 9/26/07
THE DETAILS DO NOT REFLECT THE PROPOSED CONSTRUCTION. TEH FRONT WALL DETAILS DO NOT REFLECT THE CONSTRUCTION. PROVIDE DETAIL FOR THE CONNECTION OF THE I JOIST TO THE TOP OF THE WALL.

CLEARLY INDICATE THE CONSTRUCTION OF THE MASONRY WALL.

CLEARLY ILLUSTRATE THE DETAILS FOR THE BEAM TO COLUMN CONNECTIONS

CLEARLY ILLUSTRATE THE CONSTRUCTION OF THE MASONRY COLUMNS SUPPORTING THE BEAM

PROVIDE DETAILED SECTIONS THROUGH THE BUILDING ILLUSTRATING THE CONSTRUCTION. MORE THAN ONE SECTION WILL BE REQUIRED.



FRONT SPAN OF I JOIST APPEARS TO BE OVER SPAN
09/25/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/25/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02343 9/25/07

1. Provide an electrical circuit for the rooftop GFCI.
2. Provide a cut sheet for the lighting fixtures.
3. Demonstrate source efficacy of 60 lumens per watt. Reference 2006 IECC 505.6.1.
4. Provide Disconnecting Means for EC-1. Reference NEC 430 Part IX.
5. Clarify undefined symbol in center of Electrical Plan.
09/25/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved