Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM02342
Parcel: 14118001H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02342
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2007 ROBERT SHERRY WATER REVIEW Approved
06/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems. Reference Sections 102.2 and 302.3, Uniform Administrative Code, 1997.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Section 310.0, UPC 2003.
4. Provide information to show that the hub drain complies with Sections 412.1 and 804.1, UPC 2003.
5. Clarify the drainage arrangement of S-1 and the hub drain. Reference Sections 103.2.3, 704.0, and 908.0, UPC 2003.
6. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief, and valves. Reference Sections 103.2.3, 605.5, 608.3, and 608.7 UPC 2003.
7. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference Sections 707.4 and 707.11, UPC 2003.
8. Resize the vent piping to conform to Table 7-5 (including footnote 3), UPC 2003. Reference Section 703.2, UPC 2003
06/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems. Reference Sections 102.2 and 302.3, Uniform Administrative Code, 1997.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Clarify what is being done with the existing rooftop unit (RTU-1): "Existing 5-ton RTU to remain…" per Mechanical Equipment Schedule or "Contractor to furnish and install new RTU-1 in place of the existing 4-ton unit" per the Mechanical Notes.
4. Revise the ventilation calculations to take into account the different occupancy loads (e.g. entry) in the project space. Reference Sections 403.3 and 403.3.2, IMC 2003.
5. Provide information to show that the termination of the restroom exhaust complies with the requirements of Section 401.5.2, IMC 2003.
06/11/2007 DAVE MANN FIRE REVIEW Approved
06/18/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/25/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Clarify what is being done with the existing rooftop unit (RTU-1): "Existing 5-ton RTU to remain…" per Mechanical Equipment Schedule or "Contractor to furnish and install new RTU-1 in place of the existing 4-ton unit" per the Mechanical Notes. This effects Electrical as well.
2. Coordinate Electrical requirements for EWH with Mechanical specifications. This is a 240V unit powered on 208V.
3. Count show window receptacles at 200VA per LF. Reference NEC 220.12 (A).
4. Since there is an existing feeder to RTU-1 indicated on the One-Line Diagram, show how this existing feeder is presently serving the RTU, and how it is to be intercepted in the field.
5. Please calculate demand load on Panel M according to Code. Only receptacles which are counted at no more than 180VA per outlet may use the demand factor in NEC 220.13. Count the largest motor at 125%. It appears that Circuit 3 has 633VA, not 500. It appears that Circuit 7 has 700VA, not 550. It appears that Circuit 12 has 1080VA, not 720
6. Address the possibility of other loads on this service. If this is the first tenant, indicate that the other meters and disconnecting means are for future tenants. Otherwise, provide load calculations for the electrical service for all spaces which have been permitted up to this time.
7. Provide available fault current at the service, and size of electrical service.
8. Provide fault calculations.
06/27/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) Provide approved shell building drawings to establish existing conditions.

2) Code analysis sheet is calling for separated use. Provide details for area seperation walls per chapter 7 of the 2003 IBC or correct your code analysis for nonseparated use per section 302.3.1 of the 2003 IBC.

3) Plumbing facilities required include a drinking fountain per table 2902.1 of the 2003 IBC. Please provide.

4) Door 05 may not swing into the clear floor space at the breakroom sink. Reference 2003 ANSI 117.1 section 603.2.3.

5) Provide impermeable wall coverings around water closets per 2003 IBC sec. 1210.2.

6) Provide a vertical fixed sidewall grab bar in restrooms per 2003 ANSI 117.1 section 604.5.1.

7) Plumbing pages indicate a hot water heater. Provide details for water heater support platform.

8) The ceiling grid system noted on plans exceeds local installation requirements. You may choose to delete details 5,6,7 on pp A202 and the reference to them on pp A102 if your client wishes to save the additional costs.
07/10/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
07/13/2007 SUE REEVES REJECT SHELF Completed