Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM02339
Parcel: 141012030

Address:
5336 S CIVANO BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02339
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM02339 Revised 2/15/2008

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 6/12/2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

STRUCTURAL PLANS:

1. Detail all brace wall connections from the foundation to the roof sheathing (include strapping between floors), R602.10.8.
2. Provide a complete braced panel layout showing ground floor panels with foundation connections at the southwest corner, R602.10.1.

ELEVATIONS:

1. Show the spiral stairs manufacturer, size (minimum of 60") and number of (minimum of 12) treads or risers (treads +1) on sheet A1.0 for verifying code compliance, R301.1.


If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review