Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/12/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE EGRESS ILLUMINATION WITH EMERGENCY POWER IN ACCORDANCE WITH SECTION 1006.3 OF THE 2003 IBC. COMMENT REMAINS: THE USE OF INTERIOR LIGHTING FIXTURES DOES NOT MEET THE REQUIREMENTS OF SECTION 1006.3 (#5) FOR THE EXIT DISCHARGE. PLEASE REVISE ACCORDINGLY. |
06/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The proposed point-of-use water cooler has an 1-1/2 Qt hot water tank. If this tank is greater than 3" in diameter, provide an approved temperature and pressure relief. |
06/13/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
06/13/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | |
06/13/2007 | CAGUILA1 | WWM | REVIEW | Needs Review |