Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM02274
Parcel: 12709012C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE EGRESS ILLUMINATION WITH EMERGENCY POWER IN ACCORDANCE WITH SECTION 1006.3 OF THE 2003 IBC.

2) PLEASE REVISE THE ADA VALUATION TO COMPLY WITH SECTION 3409.6 OF THE 2003 IBC. THE REUSE OF EXISTING ADA DOORS IS REQUIRED AND THEREFORE IS NOT PART OF THE 20% REQUIREMENT OF SECTION 3409.6.

3) PLEASE PROVIDE INSTALLATION DETAILS FOR THE NEW VERTICAL GRAB BARS IN ORDER TO VERIFY COMPLIANCE WITH SECTION 604.5.1 OF ANSI 117.1-2003.
06/04/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the common return plenum for the five fan coil units is to comply with the requirements of Section 606, IMC 2003. Note #7 on sheet M0.1 is not clear for this design
2. Show and label the fan coil units on the plans.
06/04/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide specifications for the point-of-use cooler noted on sheet A1.1. Add electrical circuit as necessary.
06/04/2007 ROBERT SHERRY WATER REVIEW Approved
06/04/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for the point-of-use cooler noted on sheet A1.1.
2. All fonts shall be a minimum of 1/8", all upper case (sheet A1.1).
06/04/2007 JASON GREEN ENGINEERING REVIEW Approved
06/05/2007 DAVE MANN FIRE REVIEW Approved
06/12/2007 GBONILL1 WWM REVIEW Denied
06/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/12/2007 GBONILL1 ZONING REVIEW Needs Review