Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02262
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/21/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE ADDITIONAL INFORMATION TO VERIFY COMPLIANCE WITH SECTION 3406.1 OF THE 2003 IBC REGARDING THE CHANGE OF USE FROM R2 TO B (i.e. ACCESSIBILITY, MEANS OF EGRESS, ETC.). COMMENT REMAINS: VERIFY HOW THE OFFICE AREA WILL COMPLY WITH SECTIONS 3409.3 AND 3409.6, EXCEPTION #1, OF THE 2003 IBC 2) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE LOCATION OF THE STRUCTURE IN RELATION TO THE NOTED PROPERTY LINES IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 6 OF THE 2003 IBC. THE CURRENT SUBMITTAL APPEARS TO INDICATE THAT THE PROPERTY LINES CUT THROUGH PART OF THE EXISTING STRUCTURE AND THE EGRESS STAIRS ARE ON DIFFERENT LOTS. COMMENT REMAINS: THE REQUIREMENTS OF CHAPTER 6 DO NOT ADDRESS OWNERSHIP, ONLY THE EXISTANCE OF PROPERTY LINE. IN THIS CASE, PROPERTY LINES ARE PASSING THROUGH AND IN CLOSE PROXIMITY TO THE BUILDING IN QUESTION. IN ADDITION, THE PROPERTY TO THE SOUTH APPEARS TO BE OWNED BY A SEPARATE OWNER. REFER TO ZONING COMMENTS FOR ADDITIONAL INFORMATION. 3) PLEASE PROVIDE SAFETY GLAZING IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH SECTION 2406.3 OF THE 2003 IBC (i.e. GLAZING WITHIN 24" OF A DOOR, ETC.). COMMENT REMAINS: THE REGLAZING FOR THE WINDOWS ADJACENT TO DOOR 108A AND 101A WOULD REQUIRE SAFETY GLAZING PER SECTION 2406.3 AS THEY ARE WITHIN 24" OF A DOOR, THE GLAZING NI APARTMENT 203 ADJACENT TO THE STAIR DEPENDING ON THE SILL HEIGHT, THE GLAZING IN THE BATHROOMS IN APARTMENTS 201, 208, 206 AND 205 DEPENDING ON THE SILL HEIGHT, AND THE WINDOW IN ROOM 110 DEPENDING ON THE SILL HEIGHT. 4) PLEASE PROVIDE STRUCTURAL CALCULATIONS AND FRAMING PLANS AND DETAILS FOR THE TOWER AREAS IN ORDER TO VERIFY COMPLIANCE WITH THE CURRENT CODES PER SECTION 106.1.1 OF THE 2003 IBC. COMMENT REMAINS: PLEASE HAVE THE ENGINEER OF RECORD SEAL HIS RESPONSE COMMENT. 5) PLEASE PROVIDE VERIFICATION THAT THE PROPER EXITING AND MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER HAS BEEN PROVIDED IN ACCORDANCE WITH SECTIONS 1011 AND 1006.3 OF THE 2003 IBC. COMMENT REMAINS: THE CURRENT SUBMITTAL STILL DOES NOT PROVIDE ANY INFORMATION REGARDING THE MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER ON THE EXIT DISCHARGE SIDE OF THE EXIT AND THE EXTERIOR EGRESS COMPONENTS PER SECTION 1006.3 OF THE 2003 IBC. 6) PLEASE PROVIDE VERIFICATION THAT THE CORRIDOR MEETS THE REQUIREMENTS OF SECTION 1016.1 OF THE 2003 IBC REGARDING THE REQUIRED FIRE-RESISTANCE RATING. COMMENT REMAINS: THE EXTENSION OF THE CORRIDOR THROUGH R00M 209 NOW NEEDS TO BE RATED PER SECTION 1016.1 AND DOORS INTO THIS CORRIDOR NEED TO BE RATED ACCORDINGLY. 7) PLEASE PROVIDE VERIFICATION THAT 20 PERCENT HAS BEEN SPENT INCREASING THE ACCESSIBILITY IN ACCORDANCE WITH SECTION 3409.6 OF THE 2003 IBC. COMMENT REMAINS: PLEASE PROVIDE THE CALCULATIONS ON THE PLANS THAT DENOTE THE TOTAL PROJECT COST AND THE COSTS FOR THE ITEMS THAT INCREASE ACCESSIBILITY IN ORDER TO VERIFY COMPLIANCE WITH SECTION 3409.6 OF THE 2003 IBC. 8) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE FENCE GATE IN ORDER TO VERIFY THAT IT COMPLIES WITH SECTION 1008 REGARDING THE LOCKS AND LATCHES AND CHAPTER 11 REGARDING ACCESSIBILITY. COMMENT REMAINS: THE FENCE GATE IN QUESTION IS ON THE NORTH SIDE OF THE BUILDING. PLEASE PROVIDE ADDITIONAL INFORMATION IN ORDER TO VERIFY COMPLIANCE WITH SECTION 1008 OF THE 2003 IBC. 9) PLEASE REVISE THE SIZE OF THE FONT TO A MINIMUM OF 1/8" IN HEIGHT IN ACCORDANCE WITH THE SUBMITTAL REQUIREMENTS FOR THE CITY OF TUCSON. COMMENT REMAINS: THE STRUCTURAL PLAN SHEETS HAVE NUMEROUS FONTS THAT DOES NOT COMPLY WITH THE SUBMITTAL REQUIREMENTS OF THE CITY OF TUCSON (TEXT LESS THAN 1/8" IN HEIGHT). PLEASE REVISE ACCORDINGLY. |
06/21/2007 | CHRIS KIEL (WILDAN) | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE VERIFICATION THAT THE PROPER EXITING AND MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER HAS BEEN PROVIDED IN ACCORDANCE WITH SECTIONS 1011 AND 1006.3 OF THE 2003 IBC. COMMENT REMAINS: THE CURRENT SUBMITTAL STILL DOES NOT PROVIDE ANY INFORMATION REGARDING THE MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER ON THE EXIT DISCHARGE SIDE OF THE EXIT AND THE EXTERIOR EGRESS COMPONENTS PER SECTION 1006.3 OF THE 2003 IBC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/21/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |
06/21/2007 | THAUSER1 | REJECT SHELF | Completed |