Permit Number: T07CM02262
Parcel: 11707203C

Address:
727 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02262
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2007 MICHAEL ST. PAUL ZONING REVIEW Denied Purposed structure appears to be crossing the property line.
06/01/2007 DAVE MANN FIRE REVIEW Approved
06/01/2007 CHRIS KIEL (WILDAN) ELECTRICAL-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE VERIFICATION THAT THE PROPER EXITING AND MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER HAS BEEN PROVIDED IN ACCORDANCE WITH SECTIONS 1011 AND 1006.3 OF THE 2003 IBC.
06/01/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE HAVE THE REGISTRANT OF RECORD SIGN AND DATE ALL SEALS IN ACCORDANCE WITH THE REQURIEMENTS OF THE STATE BOARD OF TECHNICIAL REGISTRATION.

2) PLEASE REVISE THE STRUCTURAL GENERAL NOTES TO REFERENCE THE ADOPTED CODES FOR THE CITY OF TUCSON PER SECTION 106.1.1 OF THE 2003 IBC.

3) PLEASE PROVIDE ADDITIONAL INFORMATION TO VERIFY COMPLIANCE WITH SECTION 3406.1 OF THE 2003 IBC REGARDING THE CHANGE OF USE FROM R2 TO B (i.e. ACCESSIBILITY, MEANS OF EGRESS, ETC.).

4) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE LOCATION OF THE STRUCTURE IN RELATION TO THE NOTED PROPERTY LINES IN ORDER TO VERIFY COMPLIANCE WITH CHAPTER 6 OF THE 2003 IBC. THE CURRENT SUBMITTAL APPEARS TO INDICATE THAT THE PROPERTY LINES CUT THROUGH PART OF THE EXISTING STRUCTURE AND THE EGRESS STAIRS ARE ON DIFFERENT LOTS.

5) PLEASE PROVIDE SAFETY GLAZING IN HAZARDOUS LOCATIONS IN ACCORDANCE WITH SECTION 2406.3 OF THE 2003 IBC (i.e. GLAZING WITHIN 24" OF A DOOR, ETC.).

6) PLEASE PROVIDE STRUCTURAL CALCULATIONS AND FRAMING PLANS AND DETAILS FOR THE TOWER AREAS IN ORDER TO VERIFY COMPLIANCE WITH THE CURRENT CODES PER SECTION 106.1.1 OF THE 2003 IBC.

7) PLEASE PROVIDE VERIFICATION THAT THE PROPER EXITING AND MEANS OF EGRESS ILLUMINATION WITH EMERGENCY POWER HAS BEEN PROVIDED IN ACCORDANCE WITH SECTIONS 1011 AND 1006.3 OF THE 2003 IBC.

8) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE EXISTING DOOR HARDWARE FOR THE DOOR INTO THE CORRIDOR ROOM 209 IN ORDER TO VERIFY COMPLIANCE WITH SECTION 1008 OF THE 2003 IBC.

9) PLEASE PROVIDE VERIFICATION THAT THE CORRIDOR MEETS THE REQUIREMENTS OF SECTION 1016.1 OF THE 2003 IBC REGARDING THE REQUIRED FIRE-RESISTANCE RATING.

10) PLEASE PROVIDE VERIFICATION THAT 20 PERCENT HAS BEEN SPENT INCREASING THE ACCESSIBILITY IN ACCORDANCE WITH SECTION 3409.6 OF THE 2003 IBC.

11) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE FENCE GATE IN ORDER TO VERIFY THAT IT COMPLIES WITH SECTION 1008 REGARDING THE LOCKS AND LATCHES AND CHAPTER 11 REGARDING ACCESSIBILITY.

12) PLEASE REVISE THE SIZE OF THE FONT TO A MINIMUM OF 1/8" IN HEIGHT IN ACCORDANCE WITH THE SUBMITTAL REQUIREMENTS FOR THE CITY OF TUCSON.
06/01/2007 JASON GREEN ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2007 THAUSER1 OUT TO CUSTOMER Completed
06/04/2007 GERARDO BONILLA REJECT SHELF Completed