Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM02255
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/08/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | 1) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE SALES TRAILER TO VERIFY THAT ACCESS INTO AND OUT OF THE TRAILER IS COMPLIANT WITH ANSI 117.1-2003. 2) PLEASE REVISE THE PLANS TO COMPLY WITH TABLE 602 OF THE 2003 IBC REGARDING SETBACK AND EXTERIOR WALL RATINGS. |
06/08/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/08/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
06/08/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02255 6/8/07 1. Equipment Grounding Conductor in the tap shall be sized according to NEC Table 250.122, or a minimum of #3. 2. Address grounding at Second Building per NEC 250.32. |
06/08/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
06/08/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/12/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |