Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02255
Parcel: 10408078C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM02255
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved 1) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE SALES TRAILER TO VERIFY THAT ACCESS INTO AND OUT OF THE TRAILER IS COMPLIANT WITH ANSI 117.1-2003.

2) PLEASE REVISE THE PLANS TO COMPLY WITH TABLE 602 OF THE 2003 IBC REGARDING SETBACK AND EXTERIOR WALL RATINGS.
06/08/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/08/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02255 6/8/07

1. Equipment Grounding Conductor in the tap shall be sized according to NEC Table 250.122, or a minimum of #3.
2. Address grounding at Second Building per NEC 250.32.
06/08/2007 DAVE MANN FIRE REVIEW Approved
06/08/2007 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2007 GERARDO BONILLA OUT TO CUSTOMER Completed