Permit Number: T07CM02243
Parcel: 13348128F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02243
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Appliances (e.g. drink dispenser, food warmer, hose reel, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2003 require backflow prevention. Specify which backflow assembly or device is to be used for each appliance. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003.
2. The provided water pressure and water pipe sizing calculations appear to be based on the developed length from the point of connection to the existing water piping and ignore the pressure drops associated with the building water meter and reduced pressure backflow prevention assembly. Revise the calculations appropriately and revise the pipe sizes as required. Reference Section 610.1, UPC 2003.
3. Comment not addressed. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Section 310.0, UPC 2003.
4. Comment not addressed: specified Asco valve not in on-line catalog. Provide the listing information for the automatic gas shut-off valve, specifically, is the valve listed for exterior application. Reference Section 1209.5, UPC 2003.
10/10/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Comment not addressed. Show that the roof top air-conditioning units supplying the additional make up air not supplied by the make up air unit for the kitchen hood are also electrically interlocked to the exhaust fans. Reference Section 508.1, IMC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
12/06/2007 CINDY AGUILAR REJECT SHELF Completed