Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02243
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Appliances (e.g. drink dispenser, food warmer, hose reel, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2003 require backflow prevention. Specify which backflow assembly or device is to be used for each appliance. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003. 2. The provided water pressure and water pipe sizing calculations appear to be based on the developed length from the point of connection to the existing water piping and ignore the pressure drops associated with the building water meter and reduced pressure backflow prevention assembly. Revise the calculations appropriately and revise the pipe sizes as required. Reference Section 610.1, UPC 2003. 3. Comment not addressed. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Section 310.0, UPC 2003. 4. Comment not addressed: specified Asco valve not in on-line catalog. Provide the listing information for the automatic gas shut-off valve, specifically, is the valve listed for exterior application. Reference Section 1209.5, UPC 2003. |
| 10/10/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Comment not addressed. Show that the roof top air-conditioning units supplying the additional make up air not supplied by the make up air unit for the kitchen hood are also electrically interlocked to the exhaust fans. Reference Section 508.1, IMC 2003. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/06/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/06/2007 | CINDY AGUILAR | REJECT SHELF | Completed |