Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02240 2/21/08

1. Indicate electrical loads on panel. It is not known from the plans whether the panel is new or existing, whether its loads are new/existing. Scope of overall work undefined.
2. Provide TEP available fault current at service and panel.
3. Provide fault current rating of service and panel.
02/25/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Install a backwater valve for the new building sewer (previously shownon the drawings dated 10/15/07). Provide a cleanout immediately downstream of the backwater valve.