Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM02240
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02240 2/21/08 1. Indicate electrical loads on panel. It is not known from the plans whether the panel is new or existing, whether its loads are new/existing. Scope of overall work undefined. 2. Provide TEP available fault current at service and panel. 3. Provide fault current rating of service and panel. |
| 02/25/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Install a backwater valve for the new building sewer (previously shownon the drawings dated 10/15/07). Provide a cleanout immediately downstream of the backwater valve. |
| 02/28/2008 | GBONILL1 | WWM | REVIEW | Needs Review |