Permit Number: T07CM02240
Parcel: 136048110

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM02240
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate what fixture will be connected to the new 4" building drain (e.g. floor sink).
2. Provide a riser diagram for the waste & vent for the new fixture.
3. Provide a cleanout immediately downstream of the backwater valve.
4. Indicate that a cleanout is required every 100 feet at least in a building sewer.
02/15/2008 CPIERCE1 WWM REVIEW Needs Review
02/15/2008 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2008 CPIERCE1 OUT TO CUSTOMER Completed