| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate what fixture will be connected to the new 4" building drain (e.g. floor sink). 2. Provide a riser diagram for the waste & vent for the new fixture. 3. Provide a cleanout immediately downstream of the backwater valve. 4. Indicate that a cleanout is required every 100 feet at least in a building sewer. |
| 02/15/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/15/2008 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |