Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T07CM02240
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/26/2007 | PETER MCLAUGHLIN | ZONING HC SITE | REVIEW | Denied | See zoning review comments. |
| 06/26/2007 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | 1. Add the zoning of adjacent parcels to the site plan. DS2-02.2.1.A.28 2. Correct the location map. The map actually represents four sections (21, 22, 27 and 28 in T14S, R 15E). Indicate that the site is within both Sections 21 and 22. Revise the scale to be correct. DS2-02.2.1.A.4 3. Indicate the correct proposed new building area in square feet in the site calculations. DS2-02.2.2.A.2 4. Indicate the height of the proposed structure in the site notes. 5. Show the location of the existing loading zone, trash receptacle, and bicycle parking on the plan to show that there is no conflict. DS2-02.2.1.A.9, A.12 and A.32. 6. Show dimensioned pedestrian system showing handicap accessible connections to the proposed kiosk. DS2-08, DS2-02.2.1.A.12 7. In addition to the standard vehicle parking space a van accessible disabled parking space, with an eight-foot aisle width is required. Show the h/c parking space and adjacent aisle on the site plan and demonstrate maneuverability for both the parking space and the vehicle wash bays. ANSI 8. Dimension setback distances to adjacent property line and to the back of future curb location along Golf Links Road, which is a designated MS&R and Gateway Route. Add a note to the site plan stating that this project meets the criteria of LUC 2.8.3, Major Streets and Routes (MS&R) Setback Zone and LUC 2.8.4, Gateway Corridor Zone. DS 2-02.2.1.A.7 9. Dimension the existing and future MS&R right-of-way (or 1/2 right-of way) width for Golf Links Road. DS 2-02.2.1.A.19 |
| 06/27/2007 | SREEVES1 | ADA | REVIEW | Passed | not a COT job |
| 07/05/2007 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Approved | |
| 07/06/2007 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 07/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the site drawing to include the finished floor elevation along with the location, invert, and rim elevation of all manholes and cleanouts. Reference City of Tucson Development Standard No. 2-05.0 2.3. 2. Confirm the size of the existing water meter. The new site plan shows it as being a ¾" meter but the reference site plan shows a 1" water meter. |
| 08/08/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Starsys DATE: August 8, 2007 Development Company 526 N. Alvernon Way Tucson, Arizona 85711 SUBJECT: Mr. Zippy's, 8687 E. Golf Links Rd. Site plan T07CM02240 (First Review) T14S, R15E, Section 22 RESUBMITTAL REQUIRED: Site Plan, Flood Plain Use permit and Hydrology Report. The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Site Plan: 1. Please include a response letter to the comments along with the corrected copies of the SP. 2. A Hydrology Report, a Flood Plain Use permit and an elevation certificate are required for this project. 3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. 4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. 5. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. 6. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19. 7. Sidewalks, curbs and wheelchair ramps are required where applicable per D.S. 3-01.3.0 and installed with "Detectable Warnings" per ADAAG. 8. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21. 9. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. 10. Show Site plan and floodplain use permit number on all sheets per D.S. 2-02.2.1.29. 11. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice. 12. List the consulting engineer and the owner/developer on the plans with the pertinent information. Hydrology Report: 1. A flood plain use permit and an elevation certificate is required for this development. 2. A Hydrology report is required for developments which are not subject to detention requirements, nor which require extensive structural improvements for handling drainage; but which are impacted by flows from significant watercourse and/or affected by 100 year flows of 100 cfs, of more….. per S.M.D.D.F.M., chap. II, 2.2 3. The content and format of the Hydrology report should follow S.M.D.D.F.M., chap. II, 2.2. 4. Show the project address or administration address on the cover sheet of the Hydrology report. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/8687 E. Golf Links Rd. Site |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/09/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/09/2007 | GERARDO BONILLA | REJECT SHELF | Completed |