Permit Number: T07CM02238
Parcel: 11451203C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM02238
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2007 DAVE MANN FIRE REVIEW Approved
07/20/2007 ROBERT SHERRY WATER REVIEW Denied 1. A Wilkins model 950XL is a double check valve assembly and is not approved for use as a backflow prevention device for this application. Reduced pressure backflow prevention assemblies shall be installed directly after the water meter for multi-use commercial buildings. This may affect the sizes of the water pipes. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Tucson water does not offer a ¾" water meter. A 5/8" meter (10 gpm maximum demand flow) and a 1" meter (25 gpm maximum demand flow) are available.
07/23/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 408 Square Feet of Office; 19,667 Square Feet of Retail; $40,111.70
07/26/2007 GERRY KOZIOL WWM REVIEW Approved
07/30/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T07CM02238
Building Plan (1st Review)

TRANSMITTAL DATE: July 30, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. The development plan will need to be reviewed as a site plan (yellow card). This review can be done over the counter as a walk through. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm02238.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
08/17/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied Provide two copies of the approved development plan, landscape and NPPO plans with the approved building plan set. A site application card (yellow card) with the CDRC approved development plan must be stamped with signatures for DSD site approval by the following reviewing sections; Fire, Zoning, Handi-cap, Engineering, Plumbing and Landscape/NPPO. The development plan may be walked through for stamps and site card sign off. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2007 DELMA ROBEY APPROVAL SHELF Completed
09/28/2007 DELMA ROBEY OUT TO CUSTOMER Completed
09/28/2007 DELMA ROBEY REJECT SHELF Completed