Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/06/2007 MARTIN HAEBERLE BUILDING-RESIDENTIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
RESIDENTIAL REVIEW COMMENTS

DATE: 6-6-07
ACTIVITY NUMBER: T07CM02225
PROJECT NAME: BARTLETT RESIDENCE
PROJECT ADDRESS: 4028 E. 17TH ST.
ARCHITECT / ENGINEER: NONE
PROJECT REVIEWER: LEERAY HANLY


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520-909-5154 OR EMAIL AT LEERAY.HANLY@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.


1. Provide previously approved plans showing existing masonry construction for exterior master bedroom wall.

2. R-19 batt insulation does not work inside 3.5" wall. Reference wall typ B ppA1.

3. Minimum R26 insulation required for dining room ceiling.

4. Please note that pp A3 is a cut through the storage bld and not the dining room.

5. Headers undersized for openings in storage room. Slider size mislabeled.

6. Smoke detector in new master bedroom to be hardwired with battery backup.

7. Arc fault protection required for all outlets in new bedroom.