Permit Number: T07CM02214
Parcel: 12405023A

Address:
811 N EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM02214
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
06/07/2007 DAVE MANN FIRE REVIEW Approved
06/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please number pages so that we have better basis for communication.
2. Page (UNNUMBERED) has design information. Shall be sealed by Registrant.
3. Electrical Diagram on Page (UNNUMBERED) indicates 208V AC system. Inverter information on Page (UNNUMBERED) indicates 240V output. Sealed drawings do not address voltage level. Please clarify.
4. Two 18 module arrays are accounted for on Sheet S-3, and on the Structural Calculations. Note 3 on Page (UNNUMBERED) makes reference to Array 3. Show this third array on Page S-3 and on Electrical Diagram Sheet (UNNUMBERED). Please note that the Structural Plans Examiner approved his plans on the basis of Arrays 1 and 2 only.
5. Electrical Diagram Sheet (UNNUMBERED) shows a termination for the Grounding Electrode Conductor. This is in violation of NEC 250.64 (C) and 250.160.
6. Please provide for marking at the 400A panel, to comply with NEC 690.64 (B) (5). Provide the exact wording.
7. The sum of the ampere ratings of the circuit breakers supplying power to the load center violates NEC 690.64 (B) (2).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
06/25/2007 GERARDO BONILLA REJECT SHELF Completed