Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM02212
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t07cm02212 7/2/07 1. Demonstrate compliance with NEC 690.9 (A) with the substitution of the SMA inverter. Provide written documentation of zero feedback, or provide the overcurrent protection. 2. Revise Electrical Notes Sheet to SMA, not Xantrex. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/11/2007 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 07/11/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |