Permit Number: T07CM02201
Parcel: 11806053C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02201
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied July 20, 2007

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701


RE: Ortiz Residence Addition – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM02201
WILLDAN PROJECT NO. 13881-7059

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
Dwelling N/A V-B 336 No ?


GENERAL COMMENTS:
All text shall be capitalized and no smaller than 1/8”. Reference IRC Section R106.1.1 and City of Tucson Submittal Requirements. Comment remains: Not addressed.


ARCHITECTURAL COMMENTS:
Reviewed and accepted.


STRUCTURAL COMMENTS:
Sheet 5
Detail gable end bracing connections. Reference IRC Sections R802.10.1, R106.1.1.


PLUMBING COMMENTS:
Not part of this review.

MECHANICAL COMMENTS:
Sheet 7
Note on plans: “Mechanical shall comply with 2003 IRC Chapters 12-24.” Reference IRC Section M1201.2. Comment remains: Not addressed.


Please clarify how heating will be provided to maintain a minimum temperature of 68° three feet above the finished floor. Reference 2003 IRC Section R303.8. Comment remains: Not addressed.


ELECTRICAL COMMENTS:
Sheet 7
Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used. Reference IRC Section E4001.6. Comment remains: Not addressed.

Please provide cut sheets and calculations for all exterior lighting fixtures, including existing fixtures. Reference City of Tucson Outdoor Lighting Code. Comment remains: Not addressed.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference City of Tucson Submittal Requirements. Comment remains: Not addressed.


ENERGY CODE COMMENTS:
Sheet 2
Indicate on the plan the “U” values of the windows, skylights, and doors in compliance with the energy calculations provided or prescriptive requirements of Chapter 11. Reference IRC Section R106.1.1. Comment remains: Not addressed.


ACCESSIBILITY COMMENTS:
Reviewed and accepted.



Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/jk

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2007 SUE REEVES OUT TO CUSTOMER Completed
07/25/2007 SUE REEVES REJECT SHELF Completed