Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02181
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate and clarify the drawings, specifications, and the energy calculations. The exterior walls are specified to have a 1" EIFS insulation board with an R-value of 3.80 per inch (Specification 07 24 00, 2.02 B (5)) and the drawings generally show 3-5/8" metal studs with batt insulation (R-11) but the calculations now show a continuous R-value of 19.0 with no cavity insulation. Reference Section 101.4, International Energy Conservation Code 2. Comment not addressed. Coordinate the condensate drain information as shown on detail 4/MP-401 with the rest of the drawings and specification #23/M.001. |
| 04/21/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. I. On the lighting code calculations, Sheet STLG-200, note that "TOTAL SHIELDED + UNSHIELDED" should be 57,676. II. Fixture GG is not specified. No wattage, source type. This was somehow wiped off of the plans. III. Fixture GB, reinstated on plans with this submittal, is unshielded in its proposed orientation. It appears that it will be necessary to eliminate some unshielded lighting in order to achieve compliance. IV. There is a break in the electrical sheets. Please reassemble the sheets such that the contents of the submittal are consistent with the Drawings List on Sheet A000. One-to-one correspondence. Sheet 304B is included in this submittal, but is not on the Drawings List. Sheet 305B is not included in this submittal, but is on the Drawings List. Sheet 401C is included in this submittal, but is not on the Drawings List. Sheet E600 is on the Drawings List, but is not included in this submittal. Typical for all which may apply. |
| 04/28/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | :NEEDS WASTEWATER DESIGN REVIEW OF EJECTOR SYSTEMS- TERRY CURLEY 740-8207 |
| 04/29/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T07CM02181 Building Plan (5th Review) TRANSMITTAL DATE: April 29, 2008 1.The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the all DSD Sections If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\grading\t07cm02181-4th.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 05/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |