Permit Number: T07CM02181
Parcel: 12504079A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02181
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/16/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate and clarify the drawings, specifications, and the energy calculations. The exterior walls are specified to have a 1" EIFS insulation board with an R-value of 3.80 per inch (Specification 07 24 00, 2.02 B (5)) and the drawings generally show 3-5/8" metal studs with batt insulation (R-11) but the calculations now show a continuous R-value of 19.0 with no cavity insulation. Reference Section 101.4, International Energy Conservation Code
2. Comment not addressed. Coordinate the condensate drain information as shown on detail 4/MP-401 with the rest of the drawings and specification #23/M.001.
04/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

I. On the lighting code calculations, Sheet STLG-200, note that "TOTAL SHIELDED + UNSHIELDED" should be 57,676.
II. Fixture GG is not specified. No wattage, source type. This was somehow wiped off of the plans.
III. Fixture GB, reinstated on plans with this submittal, is unshielded in its proposed orientation. It appears that it will be necessary to eliminate some unshielded lighting in order to achieve compliance.
IV. There is a break in the electrical sheets. Please reassemble the sheets such that the contents of the submittal are consistent with the Drawings List on Sheet A000. One-to-one correspondence. Sheet 304B is included in this submittal, but is not on the Drawings List. Sheet 305B is not included in this submittal, but is on the Drawings List. Sheet 401C is included in this submittal, but is not on the Drawings List. Sheet E600 is on the Drawings List, but is not included in this submittal. Typical for all which may apply.
04/28/2008 GERRY KOZIOL WWM REVIEW Denied :NEEDS WASTEWATER DESIGN REVIEW OF EJECTOR SYSTEMS- TERRY CURLEY 740-8207
04/29/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T07CM02181
Building Plan (5th Review)

TRANSMITTAL DATE: April 29, 2008

1.The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the all DSD Sections


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm02181-4th.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2008 SUE REEVES OUT TO CUSTOMER Completed