Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM02145 9/27/07 1. Demonstrate that neither of the electrical panels is overloaded. Sixteen amps addition is too much without load calculations. (Clarify with manufacturer how many amps the AC power requirements.) 2. Provide sizes for the main switches on the panels. 4. If 220V is indeed needed, then provide manufacturer approval to power the gates on 208V. |
10/02/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Denied |