Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02145
Parcel: 13507451C

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM02145
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM02145 9/27/07

1. Demonstrate that neither of the electrical panels is overloaded. Sixteen amps addition is too much without load calculations. (Clarify with manufacturer how many amps the AC power requirements.)
2. Provide sizes for the main switches on the panels.
4. If 220V is indeed needed, then provide manufacturer approval to power the gates on 208V.
10/02/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Denied