Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM02134
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size to a minimum of 1/8", all uppercase. 2. Provide a water riser diagram showing that the addition of the new restroom will be adequately supplied. 3. Provide an expansion tank for the new water heater. 4. Show the termination point for the T&P relief. |
| 06/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/18/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/19/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 06/19/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |