Permit Number: T07CM02134
Parcel: 13804180C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM02134
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
06/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size to a minimum of 1/8", all uppercase.
2. Provide a water riser diagram showing that the addition of the new restroom will be adequately supplied.
3. Provide an expansion tank for the new water heater.
4. Show the termination point for the T&P relief.
06/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/19/2007 GBONILL1 WWM REVIEW Needs Review
06/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/19/2007 GBONILL1 ZONING REVIEW Needs Review