Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM02134
Parcel: 13804180C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM02134
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE AN ADDITIONAL SEPARATE SEX TOILET ROOM IN ACCORDANCE WITH CHAPTER 29 OF THE 2003 IBC.

2) PLEASE PROVIDE A MINIMUM OF 5'-0" FROM THE WATER CLOSET SIDE WALL TO THE FACE OF THE LAVATORY IN ACCORDANCE WITH SECTION 604.3.1 OF ANSI 117.1-2003.

3) PLEASE PROVIDE DIMENSIONS FOR THE NEW INTERIOR WALLS IN ACCORDANCE WITH SECTION 106.1.1 OF THE 2003 IBC.

4) PLEASE SPECIFY THE HANDRAIL EXTENSION FOR THE NEW FRONT RAMP IN ORDER TO VERIFY COMPLIANCE WITH SECTION 505 OF ANSI 117.1-2003.

5) PLEASE PROVIDE SIGNAGE AT THE SECOND EXIT SPECIFYING THAT IT IS NOT AN ACCESSIBLE EXIT PER SECTION 1007.7 OF THE 2003 IBC. IF THE EXIT TO THE REAR OF THE SPACE PROVIDES AN ACCESSIBLE MEANS OF EGRESS PER SECTION 1007, THEN REVISE THE EXIT SIGNAGE ACCORDINGLY.

6) PLEASE PROVIDE A MINIMUM OF 48" IN THE HALLWAY TO THE TOILET ROOM PER SECTION 404.2.3 OF ANSI 117.1-2003 AS THE DOOR HAS A CLOSER.

7) PLEASE SPECIFY THE HEIGHT AND WIDTH FOR THE FRP WALL PANEL IN ORDER TO VERIFY COMPLIANCE WITH SECTION 1210.2 OF THE 2003 IBC.

8) PLEASE PROVIDE THE REQUIRED SIGNAGE AT THE MAIN ENTRANCE IN ACCORDANCE WITH SECTION 1008.1.8.3 (2.2) OF THE 2003 IBC.
06/04/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the revised restroom has adequate ventilation per Sections 403.2 and 403.3, IMC 2003.
06/04/2007 ANY ENGINEERING REVIEW Approved
06/04/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the waste and vent piping.
2. Show how the temperature for the lavatory is to be limited to 110 degrees Fahrenheit.
06/04/2007 MARTIN BROWN FIRE REVIEW Approved
06/04/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/04/2007 ROBERT SHERRY WATER REVIEW Approved
06/14/2007 DROBEY1 WWM REVIEW Needs Review
06/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/14/2007 DROBEY1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2007 DELMA ROBEY OUT TO CUSTOMER Completed