| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/04/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the revised restroom has adequate ventilation per Sections 403.2 and 403.3, IMC 2003. |
| 06/04/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/04/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/04/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE AN ADDITIONAL SEPARATE SEX TOILET ROOM IN ACCORDANCE WITH CHAPTER 29 OF THE 2003 IBC. 2) PLEASE PROVIDE A MINIMUM OF 5'-0" FROM THE WATER CLOSET SIDE WALL TO THE FACE OF THE LAVATORY IN ACCORDANCE WITH SECTION 604.3.1 OF ANSI 117.1-2003. 3) PLEASE PROVIDE DIMENSIONS FOR THE NEW INTERIOR WALLS IN ACCORDANCE WITH SECTION 106.1.1 OF THE 2003 IBC. 4) PLEASE SPECIFY THE HANDRAIL EXTENSION FOR THE NEW FRONT RAMP IN ORDER TO VERIFY COMPLIANCE WITH SECTION 505 OF ANSI 117.1-2003. 5) PLEASE PROVIDE SIGNAGE AT THE SECOND EXIT SPECIFYING THAT IT IS NOT AN ACCESSIBLE EXIT PER SECTION 1007.7 OF THE 2003 IBC. IF THE EXIT TO THE REAR OF THE SPACE PROVIDES AN ACCESSIBLE MEANS OF EGRESS PER SECTION 1007, THEN REVISE THE EXIT SIGNAGE ACCORDINGLY. 6) PLEASE PROVIDE A MINIMUM OF 48" IN THE HALLWAY TO THE TOILET ROOM PER SECTION 404.2.3 OF ANSI 117.1-2003 AS THE DOOR HAS A CLOSER. 7) PLEASE SPECIFY THE HEIGHT AND WIDTH FOR THE FRP WALL PANEL IN ORDER TO VERIFY COMPLIANCE WITH SECTION 1210.2 OF THE 2003 IBC. 8) PLEASE PROVIDE THE REQUIRED SIGNAGE AT THE MAIN ENTRANCE IN ACCORDANCE WITH SECTION 1008.1.8.3 (2.2) OF THE 2003 IBC. |
| 06/04/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 06/04/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a riser diagram for the waste and vent piping. 2. Show how the temperature for the lavatory is to be limited to 110 degrees Fahrenheit. |
| 06/14/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 06/14/2007 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 06/14/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |